Architecture
Neutral position without neutral
Number of protected poles 3
Number of poles 3 P
Type of pole 3 P
Concurrently switching N-neutral no
Fixing mode Din-Rail
Curve C
Controls and indicators
With fault indicator no


Main electrical features
Frequency 50/60 Hz
Rated short circuit breaking capacity Icn AC according
IEC60898-1

6 kA
Type of supply voltage AC
Rated operational voltage Ue 415 V


Voltage
Rated insulation voltage 500 V
Rated impulse withstand voltage 4000 V


Electric current
Rated short circuit breaking capacity Icn under 400V
AC according IEC60898-1

6 kA
Rated service breaking capacity Ics AC according IEC
60898-1

6 kA
Magnetic regulating currrent at 40° C 5/10 In
min/maxi threshold value of the AC thermal operation 1,13/1,45 In


Electric current / temperature
Rating current -15°C 38,61 A
Rating current -20°C 39,28 A
Rating current 0°C 36,54 A
Rating current 10°C 35,09 A
Rating current -10°C 37,93 A


Technical Properties
Rating current 15°C 34,35 A
Rating current 20°C 33,58 A
Rating current 25°C 32,8 A
Rating current -25°C 39,93 A
Rating current 30°C 32 A
Rating current 35°C 31,14 A
Rating current 40°C 30,25 A
Rating current 45°C 29,33 A
Rating current 5°C 35,82 A
Rating current -5°C 37,24 A
Rating current 50°C 28,39 A
Rating current 55°C 27,41 A
Rating current 60°C 26,39 A
Rating current 65°C 25,34 A
Rating current 70°C 24,24 A


Current correction factors
Correction factor of magnetic tripping with 100 Hz 1,1
Correction factor of magnetic tripping with 200 Hz 1,2
Correction factor of magnetic tripping with 400 Hz 1,5
Correction factor of magnetic tripping with 60 Hz 1
Correction factor of rating current for 2 devices placed
side-by-side

1
Correction factor of rating current for 3 devices placed
side-by-side

0,8
Correction factor of rating current for 4 and 5 devices
placed side-by-side

0,7
Correction factor of rating current for 6 devices placed
side-by-side

0,6

Power
Power loss per pole at In 4,9 W
Total power loss under IN 13,01 W