loading

(Not Approved) ABB MCB S202-C10 10A C-CURVE 6KA

(Not Approved) ABB MCB S202-C10 10A C-CURVE 6KA

AED0.00
star_border star_border star_border star_border star_border No reviews yet edit Write a Review
Shipping:
Calculated at Checkout
title_tag:
ABB MCB S202-C10 10A C-CURVE 6KA
description_tag:
ABB MCB S202-C10 10A C-CURVE 6KA

Product Note : Prices Subject to change with availability so please inquire first so as to get best price

System pro M compact S200 miniature circuit breakers are current limiting. They have two different tripping mechanisms, the delayed thermal tripping mechanism for overload protection and the electromechanic tripping mechanism for short circuit protection. They are available in different characteristics (B,C,D,K,Z), configurations (1P,1P+N,2P,3P,3P+N,4P), breaking capacities (up to 6 kA at 230/400 V AC) and rated currents (up to 63A). All MCBs of the product range S200 comply with IEC/EN 60898-1, IEC/EN 60947-2, UL1077 and CSA 22.2 No. 235, allowing the use for residential, commercial and industrial applications. Bottom-fitting auxiliary contact can be mounted on S200 to save 50% space.

Dimensions

Product Net Width: 35 mm
Product Net Depth: 69 mm
Product Net Height: 88 mm
Product Net Weight: 0.25 kg

Technical

Standards: IEC/EN 60898-1
IEC/EN 60947-2
UL 1077
Number of Poles: 2
Tripping Characteristic: C
Rated Current (I ): 10 A
Rated Operational Voltage: acc. to IEC 60898-1 400 V AC
acc. to IEC 60947-2 440 V AC
Power Loss: 4.2 W at Rated Operating Conditions per Pole 2.1 W
Rated Insulation Voltage (U ): acc. to IEC/EN 60664-1 440 V
Operational Voltage: Maximum (Incl. Tolerance) 125 V DC
Maximum (Incl. Tolerance) 440 V AC
Maximum 440 V AC
Maximum 125 V DC
Minimum 12 V AC
Minimum 12 V DC
Rated Frequency (f): 50 Hz/60 Hz
Rated Short-Circuit Capacity (I ): (400 V AC) 6 kA
Rated Ultimate Short-Circuit
Breaking Capacity (I ):(230 V AC) 20 kA
(440 V AC) 10 kA
Rated Service Short-Circuit
Breaking Capacity (I ):(230 V AC) 15 kA
Energy Limiting Class: 3
Overvoltage Category: III
Pollution Degree: 3
Rated Impulse Withstand Voltage
(U ):4 kV
(6.2 kV @ sea level)
(5.0 kV @ 2000 m)
Dielectric Test Voltage: 50 / 60 Hz, 1 min: 2 kV